ModeManager Safe Mode Finite State Machine

This document describes the finite state machine (FSM) for the ModeManager component's Safe Mode transitions. The ModeManager controls system operational modes and orchestrates transitions between NORMAL and SAFE_MODE based on various triggers.

State Machine Diagram

stateDiagram-v2
    [*] --> NORMAL: System Boot (clean shutdown)
    [*] --> SAFE_MODE: System Boot (unintended reboot)

    NORMAL --> SAFE_MODE: Entry Trigger
    SAFE_MODE --> NORMAL: Exit Trigger

    note right of NORMAL
        Active Components:
        - All 6 face load switches ON
        - Payload switches OFF (manual control)
        - Voltage monitoring active
        - SafeModeReason = NONE
    end note

    note right of SAFE_MODE
        Protected State:
        - All 8 load switches OFF
        - Power consumption minimized
        - SafeModeReason tracks cause
        - Safe mode sequence executed
    end note

    state NORMAL {
        [*] --> VoltageMonitoring
        VoltageMonitoring --> VoltageMonitoring: Voltage OK<br/>(Reset counter)
        VoltageMonitoring --> LowVoltageDebounce: Voltage < 6.7V<br/>(Increment counter)
        LowVoltageDebounce --> VoltageMonitoring: Voltage OK<br/>(Reset counter)
        LowVoltageDebounce --> [*]: Counter >= 10s<br/>(Trigger Safe Mode)
    }

    state SAFE_MODE {
        [*] --> ReasonCheck
        ReasonCheck --> LOW_BATTERY_Mode: Reason = LOW_BATTERY
        ReasonCheck --> MANUAL_EXIT_Mode: Reason != LOW_BATTERY

        LOW_BATTERY_Mode --> RecoveryMonitoring
        RecoveryMonitoring --> RecoveryMonitoring: Voltage < 8.0V<br/>(Reset counter)
        RecoveryMonitoring --> VoltageRecoveryDebounce: Voltage > 8.0V<br/>(Increment counter)
        VoltageRecoveryDebounce --> RecoveryMonitoring: Voltage < 8.0V<br/>(Reset counter)
        VoltageRecoveryDebounce --> [*]: Counter >= 10s<br/>(Auto-Exit)

        MANUAL_EXIT_Mode --> MANUAL_EXIT_Mode: Waiting for<br/>EXIT_SAFE_MODE<br/>command
        MANUAL_EXIT_Mode --> [*]: EXIT_SAFE_MODE<br/>command received
    }

State Transitions

Entry Transitions: NORMAL → SAFE_MODE

The ModeManager can enter SAFE_MODE from NORMAL mode through multiple triggers, each assigned a specific SafeModeReason:

Trigger SafeModeReason Description Debounce
Auto: Low Voltage LOW_BATTERY (1) Voltage drops below SafeModeEntryVoltage parameter (default: 6.7V) 10 seconds (configurable)
Command: FORCE_SAFE_MODE GROUND_COMMAND (3) Ground operator issues FORCE_SAFE_MODE command Immediate
Port: forceSafeMode EXTERNAL_REQUEST (4) or custom External component calls forceSafeMode port (e.g., watchdog timeout) Immediate
Auto: Unintended Reboot SYSTEM_FAULT (2) System boots with cleanShutdown flag = 0 in NORMAL mode At boot only
Port: forceSafeMode (LoRa) LORA (5) LoRa driver detects communication timeout/fault Immediate

Entry Actions

When entering SAFE_MODE, the ModeManager: 1. Executes the safe mode radio sequence (/seq/enter_safe.bin) 2. Sets m_mode = SAFE_MODE 3. Increments m_safeModeEntryCount (persisted) 4. Sets m_safeModeReason to the trigger reason 5. Emits one or more events: - EnteringSafeMode(reason: string) - Severity: WARNING_HI (always emitted with reason string) - AutoSafeModeEntry(reason: SafeModeReason, voltage: F32) - Severity: WARNING_HI (for LOW_BATTERY trigger) - UnintendedRebootDetected() - Severity: WARNING_HI (for SYSTEM_FAULT at boot) - ManualSafeModeEntry() - Severity: ACTIVITY_HI (for FORCE_SAFE_MODE command) - ExternalFaultDetected() - Severity: WARNING_HI (for forceSafeMode port call) 6. Turns OFF all 8 load switches via loadSwitchTurnOff ports 7. Notifies other components via modeChanged port with SAFE_MODE value 8. Executes safe mode sequence via runSequence port (may emit SafeModeSequenceCompleted or SafeModeSequenceFailed) 9. Saves state to persistent storage (/mode_state.bin)

Exit Transitions: SAFE_MODE → NORMAL

Exit from SAFE_MODE depends on the SafeModeReason:

Exit Method Conditions Applicable Reasons
Auto-Recovery Voltage > SafeModeRecoveryVoltage (default: 8.0V) for 10+ seconds LOW_BATTERY only
Manual Command Ground operator issues EXIT_SAFE_MODE command All reasons

Exit Actions

When exiting SAFE_MODE, the ModeManager: 1. Sets m_mode = NORMAL 2. Clears m_safeModeReason = NONE 3. Emits exit event: - ExitingSafeMode() - Severity: ACTIVITY_HI (manual EXIT_SAFE_MODE command) - AutoSafeModeExit(voltage: F32) - Severity: ACTIVITY_HI (auto-recovery for LOW_BATTERY) 4. Turns ON face load switches (0-5) via loadSwitchTurnOn ports - Note: Payload switches (6-7) remain OFF, requiring separate commands 5. Notifies other components via modeChanged port with NORMAL value 6. Saves state to persistent storage

Boot-Time State Restoration

On system initialization, the ModeManager: 1. Reads persistent state from /mode_state.bin 2. Restores m_mode, m_safeModeEntryCount, and m_safeModeReason 3. Checks cleanShutdown flag: - If cleanShutdown = 1: Clean boot, restore physical hardware to match saved mode - If cleanShutdown = 0 AND m_mode = NORMAL: Unintended reboot detected → Enter SAFE_MODE with reason SYSTEM_FAULT 4. Clears cleanShutdown flag (sets to 0) for next boot detection

Clean Shutdown Protocol: - The prepareForReboot port handler sets cleanShutdown = 1 before intentional reboots - This allows detection of crashes, watchdog resets, and power loss events

State Invariants

NORMAL Mode

  • m_mode = NORMAL (2)
  • m_safeModeReason = NONE (0)
  • Face load switches (0-5) are ON
  • Payload switches (6-7) are OFF (default)
  • Voltage monitoring active (1Hz via run handler)
  • Low voltage counter (m_safeModeVoltageCounter) tracks consecutive low readings
  • Recovery counter (m_recoveryVoltageCounter) is reset to 0

SAFE_MODE Mode

  • m_mode = SAFE_MODE (1)
  • m_safeModeReason = {LOW_BATTERY, SYSTEM_FAULT, GROUND_COMMAND, EXTERNAL_REQUEST, LORA}
  • All 8 load switches are OFF
  • Voltage recovery monitoring active only if reason = LOW_BATTERY
  • Recovery counter (m_recoveryVoltageCounter) tracks consecutive recovery readings (if LOW_BATTERY)
  • Low voltage counter (m_safeModeVoltageCounter) is reset to 0

Voltage Hysteresis

The ModeManager implements voltage hysteresis to prevent oscillation between modes:

  • Entry Threshold: 6.7V (configurable via SafeModeEntryVoltage parameter)
  • Recovery Threshold: 8.0V (configurable via SafeModeRecoveryVoltage parameter)
  • Gap: 1.3V hysteresis prevents rapid mode switching

Rationale: Battery voltage may fluctuate under load. The higher recovery threshold ensures the system has sufficient margin before resuming normal operations.

Debouncing Logic

All voltage-triggered transitions use a configurable debounce period (default: 10 seconds):

NORMAL → SAFE_MODE (Low Voltage):
  - Counter increments each second voltage < 6.7V
  - Counter resets to 0 if voltage >= 6.7V
  - Transition occurs when counter >= 10

SAFE_MODE → NORMAL (Auto-Recovery):
  - Counter increments each second voltage > 8.0V AND reason = LOW_BATTERY
  - Counter resets to 0 if voltage <= 8.0V
  - Transition occurs when counter >= 10

Rationale: Debouncing prevents spurious transitions due to transient voltage spikes/dips, sensor noise, or momentary load changes.

Reason-Based Recovery Rules

Only LOW_BATTERY reason allows automatic recovery. Other reasons require manual intervention:

Reason Auto-Recovery Rationale
LOW_BATTERY ✅ Yes Condition is measurable and reversible; safe to auto-recover when voltage stabilizes
SYSTEM_FAULT ❌ No Unintended reboot indicates unknown system issue; requires ground investigation
GROUND_COMMAND ❌ No Operator explicitly commanded safe mode; requires operator approval to exit
EXTERNAL_REQUEST ❌ No Another component detected a fault; requires component-specific recovery
LORA ❌ No Communication fault may indicate antenna deployment issue or ground station unavailability

Telemetry Channels

The ModeManager publishes telemetry every 1Hz via the run handler:

  • CurrentMode: U8 (1 = SAFE_MODE, 2 = NORMAL)
  • CurrentSafeModeReason: SafeModeReason enum (0-5)
  • SafeModeEntryCount: U32 (cumulative count, persisted across reboots)

Implementation Details

File Locations

  • Component Definition: PROVESFlightControllerReference/Components/ModeManager/ModeManager.fpp
  • Implementation: PROVESFlightControllerReference/Components/ModeManager/ModeManager.cpp
  • Header: PROVESFlightControllerReference/Components/ModeManager/ModeManager.hpp
  • Integration Tests: PROVESFlightControllerReference/test/int/safe_mode_test.py

Key Methods

  • run_handler(): 1Hz periodic handler for voltage monitoring and telemetry
  • enterSafeMode(reason): Transition to SAFE_MODE with specified reason
  • exitSafeMode(): Transition to NORMAL (manual command)
  • exitSafeModeAutomatic(voltage): Transition to NORMAL (auto-recovery)
  • forceSafeMode_handler(reason): Port handler for external safe mode requests
  • loadState(): Restore state from persistent storage at boot
  • saveState(): Persist state to non-volatile storage
  • prepareForReboot_handler(): Set clean shutdown flag before intentional reboot

Persistent State Structure

struct PersistentState {
    U8 mode;                 // Current mode (1 = SAFE_MODE, 2 = NORMAL)
    U32 safeModeEntryCount;  // Number of times safe mode entered
    U8 safeModeReason;       // Reason for safe mode entry (0-5)
    U8 cleanShutdown;        // Clean shutdown flag (1 = clean, 0 = unclean)
};
Stored at: /mode_state.bin (size is architecture-dependent due to struct padding, typically 8-12 bytes)

Testing Validation

The Safe Mode FSM is validated through integration tests in safe_mode_test.py:

Test Validates Status
test_safe_01 Initial reason = NONE in NORMAL mode ✅ Automated
test_safe_02 FORCE_SAFE_MODE sets reason = GROUND_COMMAND ✅ Automated
test_safe_03 EXIT_SAFE_MODE clears reason to NONE ✅ Automated
test_safe_04 GROUND_COMMAND does not auto-recover ✅ Automated
test_safe_05 Auto-entry on low voltage → reason = LOW_BATTERY ⏸️ Manual
test_safe_06 Auto-recovery on voltage recovery (LOW_BATTERY only) ⏸️ Manual
test_safe_07 Unintended reboot → reason = SYSTEM_FAULT ⏸️ Manual
test_safe_08 Clean reboot → no safe mode entry ⏸️ Manual

Design Rationale

  1. Two-State System: Simple FSM with clear separation of concerns between operational and protected states
  2. Reason Tracking: Enables intelligent recovery decisions and diagnostics
  3. Voltage Hysteresis: Prevents mode oscillation under marginal battery conditions
  4. Debouncing: Filters out transient faults and sensor noise
  5. State Persistence: Allows unintended reboot detection and mode restoration across power cycles
  6. Selective Auto-Recovery: Only measurable/reversible conditions (LOW_BATTERY) auto-recover; others require human decision
  7. Load Switch Control: Minimizes power consumption in SAFE_MODE while preserving critical functions

References